The Switch/Proximity Detector Repeater type D1130 is a DIN Rail unit with one or two independent channels.
The unit can be configured for contact or proximity detector, NO or NC and for NE or ND SPDT relay output contact.
Each channel enables a Safe Area load to be controlled by a switch, or a proximity detector, located in Hazardous Area.
D1130D dual channel type has two independent input channels and actuates the corresponding output relay. Two actuation modes can be
independently DIP switch configured on each input channel: NO In/NE relay or NO In/ND relay. Contact or proximity sensor and its
connection line short or open circuit fault detection is also DIP switch configurable: fault detection can be enabled (in case of fault it deenergizes the corresponding output relay and turns the fault LED on)or disabled (in case of fault the corresponding output relay repeats
the input line open or closed status as configured). D1130S single channel type has one input channel
Hazardous area:
Dry contact, proximity Switch
Safe area:
2 SPDT (relay contact) 2 A/250 V, plus LED for line fault detection.
Function:
1 or 2 channels I.S. switch repeater for contact or EN60947-5-6 NAMUR Prox. Provides 3 port isolation (input/output/supply).
Features:
Direct AC power module.
High density with 2 independent channels.
Field Configurable via Dip-Switches.